14
The ASCII characters are derived as per the following table:
Value Hex Value Binary Value ASCII Character ASCII Code
(Hex) (Decimal)
00 0 0000 0 30 48
01 1 0001 1 31 49
02 2 0010 2 32 50
03 3 0011 3 33 51
04 4 0100 4 34 52
05 5 0101 5 35 53
06 6 0110 6 36 54
07 7 0111 7 37 55
08 8 1000 8 38 56
09 9 1001 9 39 57
10 A 1010 : 3A 58
11 B 1011 ; 3B 59
12 C 1100 < 3C 60
13 D 1101 = 3D 61
14 E 1110 > 3E 62
15 F 1111 ? 3F 63
Examples:
I/O Line Nrs - Groups
GROUP 6 5 4 3 2 1
----- ----------- ----------- ----------- ----------- -----------
LINE # 21 20 19 18 17 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Write
Output -- -- -- -- -- -- 1 1 0 0 0 0 1 1 1 1 1 1 0 0 0 1
Command:
XOF<3?1 <CR> <LF>
Turns on Outputs 15, 14, 09, 08, 07, 06, 05, 04, 00
Turns off Outputs 13, 12, 11, 10, 03, 02, 01
GROUP 6 5 4 3 2 1
----- ----------- ----------- ----------- ----------- -----------
LINE # 21 20 19 18 17 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Read
Status 1 1 0 0 0 0 0 0 0 1 1 1 1 1 1 0 0 1 0 0 0 1
Command:
XSF <CR>
Read all lines
Response:
XS301?91 <CR><LF>
Indicates line status as in example above:
Lines 21, 20, 12, 11, 10, 09, 08, 07, 04, 00 are High (ON)
Lines 19, 18, 17, 16, 15, 14, 13, 06, 05, 03, 02, 01 are Low (OFF)