70 MLS User’s Guide
Setup
Input Type
Use this menu to configure the input sensor for each loop as one of these
input types:
Thermocouple types (J, K, T, S, R and B).
RTD. Three ranges: RTD1 (Platinum Class A), RTD2 (Platinum
Class B), and RTD3 (Nickel).
Linear and Pulse inputs.
Skip (an input type available for unused channels.) The scanning dis-
play doesn't show loops you've set to Skip.
The next table shows the MLS' input types and ranges.
Input
Type
Fahrenheit
Range
Celsius Range
J -350 to +1400 -212 to +760
K -450 to +2500 -268 to +1371
T -450 to +750 -268 to +399
S 0 to +3200 -18 to +1760
R 0 to +3210 -18 to +1766
B +150 to +3200 +66 to +1760
RTD1 -148.0 to +572.0 -100.0 to +300.0
RTD2 -184 to +1544 -120 to +840
RTD3 -94 to 572 -70 to 300
Pulse 0-2 KHz
Skip Loop is not scanned or displayed.
Linear see the
Linear Scaling section
(this chap-
ter) and
Appendix
.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
06 INPUT TYPE?