Watlow EZ-ZONE ST User Manual Page 52

  • Download
  • Add to my manuals
  • Print
  • Page
    / 97
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 51
Watlow EZ-ZONE
®
ST 50 Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[A;dSP]
[A.dSP]
Alarm (1 to 2)
Display
Display an alarm message
when an alarm is active.
[`oFF] Off (62)
[``on] On (63)
On Instance 1
Map 1 Map 2
- - - - 1480
Instance 2
Map 1 Map 2
- - - - 1540
0x6D
(109)
1 to 2
0x10 (16)
30 9016 Inst. 1
1510
Inst. 2
1560
uint
RWES
[`A;dL]
[ A.dL]
Alarm (1 to 2)
Delay
Set the span of time that
the alarm will be delayed
after the process value ex-
ceeds the alarm set point.
0 to 9,999 seconds 0 Instance 1
Map 1 Map 2
- - - - 1490
Instance 2
Map 1 Map 2
- - - - 1550
0x6D
(109)
1 to 2
0x15 (21)
31 9021 - - - - uint
RWES
[CUrr]
[`Set]
Current Menu
[`C;Sd]
[ C.Sd]
Current (1)
Sides
Select which side or sides
will be monitored.
[`oFF] Off (62)
[high] High (37)
[low] Low (53)
[both] Both (13)
Off Instance 1
Map 1 Map 2
283 1248
0x73 (115)
1
5
145 15005 Inst. 1
1128
uint
RWES
[`C;Ur]
[ C.Ur]
Current (1)
Message Enable
Display under/ over range
current.
No (59)
Yes (106)
No Instance 1
Map 1 Map 2
- - - - 1246
0x73 (115)
1
4
146 15004 Inst. 1
1126
uint
RWES
[`C;le]
[ C.LE]
Current (1)
Current Limit Trip En-
able
No (59)
Yes (106)
No Instance 1
Map 1 Map 2
284 1250
0x73 (115)
1
6
- - - - 15006 Inst. 1
1130
uint
RWES
[C;;oFs]
[C.oFS]
Current (1)
Heater Offset
Apply an offset to the cur-
rent reading
-9,999.000 to 9,999.000 0.0 Instance 1
Map 1 Map 2
- - - - 1260
0x73 (115)
1
0xB (11)
149 15011 Inst. 1
1140
float
RWE
No Dis-
play
Current (1)
Current Gain
-1,999.000 to 9,999.000 100.0 Instance 1
Map 1 Map 2
290 1258
0x73 (115)
1
0xA (10)
- - - - - - - - Inst. 1
1138
float
RWE
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EE-
PROM
S: User
Set
Page view 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 96 97

Comments to this Manuals

No comments