Watlow EZ-ZONE ST User Manual Page 50

  • Download
  • Add to my manuals
  • Print
  • Page
    / 97
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 49
Watlow EZ-ZONE
®
ST 48 Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[`o;tb]
[ o.tb]
Output (1 to 4)
Time Base
Set the time base for
fixed-time-base control.
0.1 to 60.0 seconds (solid-state
relay or switched dc)
5.0 to 60.0 seconds (mechani-
cal relay or no-arc power
control)
0.1 sec.
[SSR &
sw dc]
20.0 sec.
[mech,
relay, no-
arc]
Instance 1
Map 1 Map 2
132 944
[Map1 Offset
+ 13]
[Map2 Offset
+ 30]
0x6A
(106)
1 to 4
3
86 6003 Inst. 1
884
Offset
+ 30
float
RWES
[`o;Lo]
[ o.Lo]
Output (1 to 4)
Low Power Scale
The power output will
never be less than the
value specified and will
represent the value at
which output scaling
begins.
0.0 to 100.0% 0.0% Instance 1
Map 1 Map 2
139 956
[Map1 Offset
+ 13]
[Map2 Offset
+ 30]
0x6A
(106)
1 to 4
9
87 6009 Inst. 1
896
Offset
+ 30
float
RWES
[`o;hi]
[ o.hi]
Output (1 to 4)
High Power Scale
The power output will
never be greater than
the value specified and
will represent the value
at which output scaling
stops.
0.0 to 100.0% 100.0% Instance 1
Map 1 Map 2
141 958
[Map1 Offset
+ 13]
[Map2 Offset
+ 30]
0x6A
(106)
1 to 4
0xA (10)
88 6010 Inst. 1
898
Offset
+ 30
float
RWES
[``Fn]
[ Fn]
Output (1)
Function
Select what function will
drive this output.
[`oFF] Off (62)
[heat] Heat, Control Loop
(36)
[Cool] Cool, Control Loop
(20))
off Instance 1
Map 1 Map 2
- - - - 782
0x6A
(118)
1
2
- - - - 18002 - - - - uint
RWES
[ss;ti]
[SS.ti]
Output (1)
Soft Start Time
Set the time (in seconds)
it takes to achieve 100%
power
0.0 to 1000.0 seconds 0 Instance 1
Map 1 Map 2
- - - - 820
0x76 (118)
1
0x15 (21)
- - - - 18021 - - - - float
RWES
[Alm]
[`Set]
Alarm Menu
[`A;ty]
[ A.ty]
Alarm (1 to 2)
Type
Select whether the alarm
trigger is a fixed value or
will track the set point.
[`oFF] Off (62)
[PR;AL] Process Alarm (76)
[dE;AL] Deviation Alarm (24)
Off Instance 1
Map 1 Map 2
110 1478
Instance 2
Map 1 Map 2
126 1538
0x6D
(109)
1 to 2
0xF (15)
20 9015 Inst. 1
1508
Inst. 2
1558
uint
RWES
[`sr;a]
[ Sr.A]
Alarm (1 to 2)
Source Function A
Select what will trigger
this alarm.
[``Ai] Analog Input (142)
[CUrr] Current (22)
[PWr] Power, Control Loop
(73)
Instance 1
Map 1 Map 2
111 1482
Instance 2
Map 1 Map 2
127 1542
0x6D
(109)
1 to 2
0x11 (17)
21 9017 Inst. 1
1512
Inst. 2
1562
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EE-
PROM
S: User
Set
Page view 49
1 2 ... 45 46 47 48 49 50 51 52 53 54 55 ... 96 97

Comments to this Manuals

No comments