Watlow Series 93 Setup 4.7
Setup
Operation Parameters Value Range Factory Default
[`Pb1] If [`dFL] is set to [``US]:
0 to 555°C/0 to 999°F/0 to 999 Units 25°F
0 to 55.5°C/0 to 99.9°F/0 to 99.9 Units 2.5°F
0 is control. [`HSC] is set to switch differential
If [`dFL] is set to [``SI]:
0.0 to 999.9% of span 3%
[`rE1] 0.00 to 9.99 repeats/minute 0.00 repeats/minute
0.00 = No Reset. Won't appear if [`Pb1] is set to 0
or [`dFL] is set to [``SI].
[`It1] 0.0 to 99.9 minutes/repeat. 0.00 = No Integral. 00.0 minutes/repeat
Won't appear if [`Pb1] is set to 0 or [`dFL] is set to [``US].
[`rA1] 0.00 to 9.99 minutes 0.00 minutes
0.00 = No Rate. Will not appear if [`Pb1] is set to 0
or [`dFL] is set to [``SI].
[`dE1] 0.00 to 9.99 minutes. 0.00 = No Derivative. 0.00 minutes
Won't appear if [`Pb1] is set to 0 or [`dFL] is set to [``US].
[`Ct1] 0.1 to 999.9 5.0 seconds
Won't appear if [`Pb1] is set to 0, or [`420].
[`Pb2] Same as [`Pb1]. [`Pb2] lower limit = 1, 0.1, 0.01
[`rE2] Same range as [`rE1].
[`It2] Same range as [`It1].
[`rA2] Same range as [`rA1].
[`dE2] Same range as [`dE1].
[`Ct2] Same range as [`Ct1].
[`ALO] Deviation [``dE] -999 to 0 -999
Process [``Pr] [``rL] to [`AHI] [``rL]
Will not appear if [`Ot2] is set to [``no] or [`Con].
[`AHI] Deviation [``dE] 0 to 999 999
Process [``Pr] [`ALO] to [``rH] [``rH]
Will not appear if [`Ot2] is set to [``no] or [`Con].
[`CAL] ±100°C/±180°F/±180 Units 0
[`AUt] 0 to 3 0
If a mechanical relay or contactor is switching power to the load, a longer
cycle time may be desirable to minimize wear on the mechanical compo-
nents. Typical life of a mechanical relay is 100,000 cycles.
Range: 0.1 to 999.9 seconds Default: 5.0 seconds
Alarm Low: Represents the low process alarm or low deviation alarm. This para-
meter will not appear if [`Ot2] is set to no or [`Con].
Range if [`Ot2] is set to [`dEA] or [``dE]: -999 to 0 Default: -999
Range if [`Ot2] is set to [`PrA] or [``Pr]: [``rL] to [`AHI] Default: [``rL]
Alarm High: Represents the high process alarm or high deviation alarm. This
parameter will not appear if [`Ot2] is set to [``no] or [`Con].
Range if [`Ot2] is set to [`dEA] or [``dE]: 0 to 999 Default: 999
Range if [`Ot2] is set to [`PrA] or [``Pr]: [`ALO] to [``rH] Default: [``rH]
Calibration Offset: Adds or subtracts degrees from the input signal.
Range: -100°C to 100°C/-180°F to 180°F/-180 units to 180 units; or
-10.0°C to 10.0°C/-18.0°F to 18.0°F Default: 0
Autotune: Initiates an autotune.
Range: 0 is set to off, 1 is set to slow, 2 is set to medium, 3 is set to fast
Default: 0
Table 4.7 -
Operation Menu
Prompts and
Descriptions.
{`ALO}
Operation Menu
Document your Series 93 Operation Parameters in the Value column below.
Do not mark any values here; make photocopies instead.
{`AHI}
{`AUt}
{`CAL}