Watlow EZ-ZONE PM User Manual Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 111
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
Warning: Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or
peripheral devices. Failure to do so
may result in damage to equipment
and property, and/or injury or loss
of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination or
two 1.31 mm
2
(16 AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation be-
tween Analog Input 1, Digital I/O,
Switched dc/open collector outputs
and Process outputs to prevent
ground loops.
Note:
The control output common
terminal and the digital common
terminal are referenced to different
voltages and must remain isolated.
Watlow EZ-ZONE
®
PM Limit Controller 32 Chapter 2 Install and Wire
Connecting a Computer to PM Controls Using B&B 485 to USB Converter
USB
Port
EZ-ZONE
®
PM
to B&B Converter
Model ULINX 485USBTB-2W
USB to RS-485 Adapter
using Standard Bus
TM
PM6_ _ _ _-A_ _ _A_ _
PM6_ _ _ _-A_ _ _A_ _
O
u
t
p
u
t
1
O
u
t
p
u
t
1
O
u
t
p
u
t
2
O
u
t
p
u
t
2
I
n
p
u
t
1
I
n
p
u
t
1
O
u
t
p
u
t
3
O
u
t
p
u
t
3
O
u
t
p
u
t
4
O
u
t
p
u
t
4
I
n
p
u
t
2
I
n
p
u
t
2
D
I
/
O
5
&
6
D
I
/
O
5
&
6
4
8
5
C
o
m
m
s
4
8
5
C
o
m
m
s
P
o
w
e
r
P
o
w
e
r
CF
CF
CD
CD
CE
CE
S
l
o
t
A
S
l
o
t
A
S
l
o
t
B
S
l
o
t
B
S
l
o
t
C
S
l
o
t
C
A
A
C
C
B
B
Address 1 Address 2
Use twisted pair wires such as Cat 5 cabling.
Do not route with power carrying conductors.
Daisy chain wire up to 16 EZ-ZONE devices.
Æ
http://www.bb-elec.com/
LINX
Model 485TB-2W
U
S
B
A(-)
A(-)
B(+)
B(+)
GND
B B electronics&
TM
U
USB Serial Conversion
PC Software Protocol - Standard Bus
EZ Configurator
Data format
38,400 baud
8 data bits
no parity
1 start bit
1 stop bit
0847-0326-0000
Æ
RESET
L
I
M
I
T
L
I
M
I
T
PM6 [L,M] _ _ _ _ - A A _ _ A A A
PM6 [L,M] _ _ _ _ - A A _ _ A A A
WATLOW
WATLOW
EZ-ZONE
TM
EZ-ZONE
TM
RESET
Note:
DonotleaveaUSBtoEIA-485converterconnectedtoStandardBuswithout
power (i.e., disconnecting the USB end from the computer while leaving the
converterconnectedonStandardBus).DisturbanceontheStandardBus
may occur.
Note:
When connecting the USB converter to the PC it is suggested that the La-
tencyTimerbechangedfromthedefaultof16msecto1msec.Failureto
make this change may cause communication loss between the PC running
EZ-ZONE Configurator software and the control.
To modify Latency Timer settings follow the steps below:
1.NavigatetoDeviceManager.
2.DoubleclickonPorts.
3.RightclickontheUSBserialportinuseandselectProperties.
4. Click the tab labeled Port settings and then click the Advance button.
Page view 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 110 111

Comments to this Manuals

No comments