Watlow EZ-ZONE PM User Manual Page 53

  • Download
  • Add to my manuals
  • Print
  • Page
    / 111
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 52
Watlow EZ-ZONE
®
PM Limit Controller 50 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`i;Ca]
[ i.CA]
Analog Input (1)
Calibration Offset *
Offset the input reading
to compensate for lead
wire resistance or other
factors that cause the
input reading to vary
from the actual process
value.
-1,999.000to9,999.000°For
units
-1,110.555to5,555.000°C
0.0 Instance 1
Map 1 Map 2
382 382
0x68(104)
1
0x0C(12)
2 4012 float
RWES
[`Ain]
[ Ain]
Analog Input (1)
Analog Input Value *
View the process value.
Note:
Ensure that the Input
Error Status (below)
indicatesnoerror(61)
when reading this
value using a field bus
protocol. If an error
exists, the last known
value prior to the er-
ror occurring will be
returned.
-1,999.000to9,999.000°For
units
-1,128.000to5,537.000°C
- - - - Instance 1
Map 1 Map 2
360 360
0x68(104)
1
1
0 4001 float
R
[`i;Er]
[ i.Er]
Analog Input (1)
Input Error Status *
View the cause of the
most recent error. If
the
[Attn]
message is
[Er;i1]
, this parameter
will display the cause of
the input error.
[nonE]None(61)
[OPEn] Open (65)
[Shrt]Shorted(127)
[`E;M] Measurement Error
(149)
[E;CAL] BadCalibrationData
(139)
[Er;Ab] Ambient Error (9)
[E;;Rtd] RTDError(141)
[FAiL]Fail(32)
[Nsrc] Not Sourced (246)
None Instance 1
Map 1 Map 2
362 362
0x68(104)
1
2
1 4002 float
R
[`dio]
[`Set]
Digital Input/Output Menu
[`dir]
[ dir]
Digital Input/Output
(5 to 6)
Digital I/O Direction
Set this function to
operate as an input or
output.
[OtPt] Output (68)
[iCon]InputDryContact
(44)
[``in]InputVoltage(193)
Output Instance 5
Map 1 Map 2
1000 1120
Offset to next
instance (Map
1 & Map 2)
equals+30
0x6A(106)
5 to 6
1
82 6001 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
* These parameters/prompts are available in this menu with firmware revisions 11.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set
Page view 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 110 111

Comments to this Manuals

No comments