PM Limit Controller 75 • Chapter 8 Features
10. ReadElectricalMeasurementvalue[`Mu] of controller via EZ-Configurator or RUI. This will be re-
ferred to as Electrical Measured High. Record high value ______________
11. CalculatedElectricalInputSlope=(PrecisionHigh–PrecisionLow)/(ElectricalMeasuredHigh-Elec-
trical Measured Low). Calculated Slope value ___________
12. CalculatedElectricalInputOffset=PrecisionLow–(ElectricalInputSlope*MeasuredLow).Calculated
Offset value ___________
13. EnterthecalculatedElectricalInputSlope[ELi;S] and Electrical Input Offset [ELi;o] into the control-
ler.
14. Exitcalibrationmenu.
15. Validatecalibrationprocessbyutilizingacalibratortotheanaloginput.
16. Entercalibrationoffsetasrecordedinstep2ifrequiredtocompensateforsensorerror.
Setting Electrical Input Slope [ELi;S]to1.000andElectricalInputOffset[ELi ;o] to 0.000, restores factory
calibration as shipped from factory.
Filter Time Constant
Filtering smoothes an input signal by applying a first-order filter time constant to the signal. Filtering the
displayedvaluemakesiteasiertomonitor.FilteringthesignalmayimprovetheperformanceofPIDcontrol
in a noisy or very dynamic system.
Adjust the filter time interval with Filter Time [`FiL] (Setup Page, Analog Input Menu).
Example:Withafiltervalueof0.5seconds,iftheprocessinputvalueinstantlychangesfrom0to100andre-
mainedat100,thedisplaywillindicate100afterfivetimeconstantsofthefiltervalueor2.5seconds.
Sensor Selection
Youneedtoconfigurethecontrollertomatchtheinputdevice,whichisnormallyathermocouple,RTDor
process transmitter. When you select an input device, the controller automatically sets the input linearization
to match the sensor. It also sets high and low limits, which in turn limit the set point range-high and range-
low values.
Select the sensor type with Sensor Type [`Sen] (Setup Page, Analog Input Menu).
Note:
The EZ-ZONE PM does not have an open-sensor detection feature for process inputs.
Set Point Low Limit and High Limit
The controller constrains the Limit set point to a value between the Set Point Low Limit and the Set Point
High Limit.
Set the set point range with Set Point Low Limit [sp;ll] and Set Point HighLimit [sp;lh] (Setup Page,
Loop Menu).
Unfiltered Input Signal
Time
Temperature
Filter Time Constant
Filtered Input Signal
Time
Temperature