Watlow EZ-ZONE
®
PM Limit Controller 42 Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[``Ai]
[oPEr]
Analog Input Menu
[`Ain]
[ Ain]
Analog Input (1)
Analog Input Value
View the process value.
Note:
Ensure that the Input Er-
ror (below) indicates no
error(61)whenreading
this value using a field
bus protocol. If an error
exists, the last known
value prior to the error oc-
curring will be returned.
-1,999.000to
9,999.000°Forunits
-1,128.000to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
360 360
0x68(104)
1
1
0 4001 float
R
[`i;Er]
[ i.Er]
Analog Input (1)
Input Error
View the cause of the most
recent error. If the
[Attn]
message is
[Er;i1]
, this
parameter will display the
cause of the input error.
[nonE]None(61)
[OPEn] Open (65)
[FAiL]Fail(32)
[Shrt]Shorted(127)
[`E;M] Measurement
Error(140)
[E;CAL] Bad Calibration
Data(139)
[Er;Ab] Ambient Er-
ror (9)
[E;;Rtd] RTDError(141)
[Nsrc] Not Sourced
(246)
None Instance 1
Map 1 Map 2
362 362
0x68(104)
1
2
1 4002 uint
R
[`i;Ca]
[ i.CA]
Analog Input (1)
Calibration Offset
Offset the input reading to
compensate for lead wire
resistance or other factors
that cause the input reading
to vary from the actual pro-
cess value.
-1,999.000to
9,999.000°Forunits
-1,110.555to
5,555.000°C
0.0 Instance 1
Map 1 Map 2
382 382
0x68(104)
1
0xC(12)
2 4012 float
RWES
[`dio]
[oPEr]
Digital Input/Output Menu
[`do;S]
[ do.S]
Digital Output (5 to 6)
Output State
View the state of this out-
put.
[`off] Off (62)
[``on]On(63)
- - - - Instance 5
Map 1 Map 2
1012 1132
Offset to next
instance equals
+30
0x6A(106)
5 to 6
7
90 6007 uint
R
[`di;S]
[ di.S]
Digital Input (5 to 6)
Input State
View this event input state.
[`off] Off (62)
[``on]On(63)
- - - - Instance 5
Map 1 Map 2
1020 1140
Offset to next
instance equals
+30
0x6A(106)
5 to 6
0xB(11)
- - - - 6011 uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.