Technical Reference
WATLOW Series 1500 User's Manual 41
Programming, Chapter 4
Programming CHG DATA
CAUTION:
Be sure DIP SW-6
is in the OFF
(Warm Start)
position before
you begin pro-
gramming; all your
entries will be
saved when power
Normally, the 1500 should be in the Warm Start condition. In Cold Start, all program
information will be lost when power is applied to the unit.
DIP Switch #7 sets the temperature scale at °C or °F.
DIP Switch #8 is not used, set it to the OFF position.
Recycle Option
You may request that your program repeat indefinitely by selecting RC=1 in the
GA = 6 area of the CHG PARA mode.
With the Recycle option active, you may expect to see continuous activity as the
program sequence repeats. However, if your Step #1 is programmed as a "Wait
Step," the processor will be waiting for a time or actual condition and no action will
be taking place.
Programming in General
The programming method is simple. Press the MODE key to get to the mode you
want to program. Then use the FCTN key to move from one prompt to the next for
each of the displays.
When you want to enter data at any given FUNCTION display prompt, press the UP
or DOWN key to select the data for the DATA display. Then, press the ENTER key
to enter the data. The display will momentarily blank, then the entered data will re-
appear for a short duration and then self-prompt to the next parameter. Whenever
you press the MODE key, you'll get an immediate exit from any mode the 1500 is in.
The flow diagrams, Figures 15 and 16, will aid you in understanding the programming
process for CHG DATA and CHG PARA, respectively.
Programming the Change Data Mode (CHG DATA)
Press the MODE key to select the CHANGE DATA mode. The processor will auto-
matically branch to one of three submodes or Step Types: SP-Set Point,
JL-Jump Loop, WT-Wait. See Figure 15.
When SP is in the FUNCTION window and the DATA window is blank, the 1500 is
displaying a "blank step." A blank step is simply an unprogrammed step.
1. For SP (Set Point) submode, press ENTER. The display responds with S1 and
the DATA window is blank. This means the set point for Channel 1 on this
particular step is not programmed. If you want to ENTER a set point for
Channel 1, select a value and press ENTER. Or, if you do not want to program
S1, just press FCTN, and display shows S2. The DATA window is again blank.
2. For the JL (Jump Loop) submode, press FCTN until JL appears in the FUNC
TION window. Then press ENTER. JS-Jump Step, and JC-Jump Count are the
parameters to be entered next.
Page view 40