Technical Reference
WATLOW Series 1500 User's Manual 47
Programming, Chapter 4
This section will
also vary accord-
ing to the flow
chart depending
upon DIP Switch
#4 (single or dual
PID).
Guarded Access
minutes with the UP/DOWN keys. Press ENTER. The prompt SC will appear.
Select correct seconds with the UP/DOWN keys. Press ENTER; GA will appear.
GA (Guarded Access) Programming
The Guarded Access parameters control the process limits. The three GA parame-
ter loops are restricted to operators by special codes. The Guarded Access codes
prevent inexperienced or unauthorized operators from changing the parameters.
The GA prompts appear in the Guarded Access Charts (p. 49 or 50) and in the CHG
PARA flow diagram. You may alter any one of them by changing the DATA display
with the UP and DOWN keys. Then press ENTER. Guarded Access parameters will
not self prompt. To proceed to the next prompt, press FCTN.
GA (Guarded Access) Select a GA code with the UP and DOWN keys. Then
press ENTER. The first prompt in the loop appears.
GA Code = 0000. Prompts appear for Ch-1, then repeat for Ch-2. These
parameters are more fully explained in the "Alarm" reference section, p. 46.
Ranges for your particular unit are in the charts on pages 49 or 50.
UP (Upper Process Type Alarm) Select an alarm point of this type for Ch-1.
Press ENTER; press FCTN. If you do not want this alarm set to highest value.
LP (Lower Process Type Alarm) Select an alarm point of this type for Ch-1.
Press ENTER; press FCTN. If you do not want this alarm set to lowest value.
Ud (Upper Deviation Type Alarm) Select an alarm point of this type for Ch-1.
Press ENTER; press FCTN. If you do not want this alarm set to highest value.
Ld (Lower Deviation Type Alarm) Select an alarm point of this type for Ch-1.
Press ENTER; press FCTN. If you do not want this alarm set to lowest value.
Sequence repeats for Channel 2 and then leaves the guarded area, returning to
real time.
GA Codes = 0001 and 0002. Prompts appear for Ch-1 with Code 0001, and then
repeat for Ch-2 with Code 0002. Except for CA, these parameters pertain
directly to tuning your control to the system. See the "Tuning" reference section
on p. 60. Ranges and default values are listed on pp. 49 or 50.
Pb (Proportional Band) Select a proportional band value with the UP/DOWN
keys. Then press ENTER; press FCTN.
RS (Reset) Select a reset value with the UP/DOWN keys. Then press ENTER;
press FCTN.