Watlow Series F4S/D Operations 3.11
Operations Page Parameter Table Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default [I/O, Set, Ch] Parameters to Appear
*This section is also applicable for Cascade Inner Loop.
NOTE: For more information about how parameter settings
affect the controller’s operation, see the Features Chapter.
Active if PID Units (Setup Page)
is set to SI and Proportional
Band is not set to 0.
1A 1B Set
503 553 [1]
513 563 [2]
523 573 [3]
533 583 [4]
543 593 [5]
r/w
0.00 minutes
(0)
0.00 to 9.99 minutes
(0 to 999)
Derivative x (A or B)
Set the derivative
time.
Active if PID Units (Setup Page)
is set to U.S. and Proportional
Band is not set to 0.
1A 1B Set
502 552 [1]
512 562 [2]
522 572 [3]
532 582 [4]
542 592 [5]
r/w
0 per minute
(0)
0.00 per minute to
99.99 per minute
(0 to 9999)
Reset x (A or B)
Set the reset time in
repeats per minute.
Active if PID Units (Setup Page)
is set to SI and Proportional
Band is not set to 0.
1A 1B Set
501 551 [1]
511 561 [2]
521 571 [3]
531 581 [4]
541 591 [5]
r/w
0 minutes
(0)
0.00 to 300.00 minutes
(0 to 30000)
Integral x (A or B)
Set the integral time
in minutes.
Active: Always (Channel 1).
°F Default for US
°C Default for SI
1A 1B Set
500 550 [1]
510 560 [2]
520 570 [3]
530 580 [4]
540 590 [5]
r/w
25°F (25)
14°C (14)
0 to 30000
(0 to 30000)
Proportional Band x (A or B)
Define the propor-
tional band for PID
control.
Main > Operations > Edit PID > PID Set Channel 1 > PID Set x (1 to 5)
PID Set x (1 to 5)* (Optional Inner Loop)
Main > Operations > Edit PID
Edit PID
Active if Analog Input 3 Control
Type is set to Cascade.
343
r/w
Tune Off (0)Tune Off (0)
Outer Loop PID Set 1 (1)
Outer Loop PID Set 2 (2)
Outer Loop PID Set 3 (3)
Outer Loop PID Set 4 (4)
Outer Loop PID Set 5 (5)
Cascade Outer Loop
Select which PID pa-
rameters will be au-
tomatically tuned.
Active if Analog Input 3 Control
Type is set to Cascade.
305
r/w
Tune Off (0)Tune Off (0)
Inner Loop PID Set 1 (1)
Inner Loop PID Set 2 (2)
Inner Loop PID Set 3 (3)
Inner Loop PID Set 4 (4)
Inner Loop PID Set 5 (5)
Cascade Inner Loop
Select which PID pa-
rameters will be au-
tomatically tuned.
Main > Operations > Autotune PID > Cascade
Autotune PID Cascade
Active: Always (Channel 1).
Active if controller is set to Dual
Channel Ramping (Channel 2).
Channel
305 [1]
324 [2]
r/w
Tune Off (0)Tune Off (0)
Ch1 PID Set 1 (1)
Ch1 PID Set 2 (2)
Ch1 PID Set 3 (3)
Ch1 PID Set 4 (4)
Ch1 PID Set 5 (5)
Ch2 PID Set 6 (1)
Ch2 PID Set 7 (2)
Ch2 PID Set 8 (3)
Ch2 PID Set 9 (4)
Ch2 PID Set 10 (5)
Channel x (1 to 2) Autotune
Select whether PID
parameters will be
automatically
selected.
Main > Operations > Autotune PID
Autotune PID