Watlow Series F4S/D User Manual Page 78

  • Download
  • Add to my manuals
  • Print
  • Page
    / 152
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 77
103 % Power Output 1A, Status
r0 to 100
(expressed in %)
107 % Power Output 1B, Status
r0 to 100
(expressed in %)
111 % Power Output 2A, Status
r0 to 100
(expressed in %)
115 % Power Output 2B, Status
r0 to 100
(expressed in %)
102 Alarm 1, Status
r
106 Alarm 2, Status
r
303 Alarm High Deviation, Alarm 1, Value
r/w 1 to 30000
322 Alarm High Deviation, Alarm 2, Value
r/w 1 to 30000
303 Alarm High Set Point, Alarm 1, Value
r/w <per sensor> to Alarm 1 Low Set Point
322 Alarm High Set Point, Alarm 2, Value
r/w <per sensor> to Alarm 2 Low Set Point
703 Alarm Hysteresis, Alarm Output 1
r/w 1 to 30000
720 Alarm Hysteresis, Alarm Output 2
r/w 1 to 30000
704 Alarm Latching, Alarm Output 1
r/w 0 Alarm Self-clears
1 Alarm Latches
721 Alarm Latching, Alarm Output 2
r/w 0 Alarm Self-clears
1 Alarm Latches
707 Alarm Logic, Alarm Output 1
r/w 0 Open on Alarm
1 Close on Alarm
724 Alarm Logic, Alarm Output 2
r/w 0 Open on Alarm
1 Close on Alarm
302 Alarm Low Deviation, Alarm 1, Value
r/w -19999 to -1
321 Alarm Low Deviation, Alarm 2, Value
r/w -19999 to -1
302 Alarm Low Set Point, Alarm 1, Value
r/w <per sensor> to Alarm 1 High Set Point
321 Alarm Low Set Point, Alarm 2, Value
r/w <per sensor> to Alarm 2 High Set Point
708 Alarm Messages, Alarm Output 1
r/w 0 Yes on Main Page
1No
725 Alarm Messages, Alarm Output 2
r/w 0 Yes on Main Page
1No
1308 Alarm Set Point, Lockout
r/w 0 Full Access
1 Read Only
2 Password
3 Hidden
706 Alarm Sides, Alarm Output 1
r/w 0 Both
1 Low
2 High
723 Alarm Sides, Alarm Output 2
r/w 0 Both
1 Low
2 High
705 Alarm Silencing, Alarm Output 1
r/w 0 No
1Yes
722 Alarm Silencing, Alarm Output 2
r/w 0 No
1Yes
716 Alarm Source, Alarm Output 1
r/w 0 Input 1
1 Input 2
2 Input 3
733 Alarm Source, Alarm Output 2
r/w 0 Input 1
1 Input 2
2 Input 3
702 Alarm Type, Alarm Output 1
r/w 0 Off
1Process
2 Deviation
719 Alarm Type, Alarm Output 2
r/w 0 Off
1Process
2 Deviation
1902 Altitude, Analog Input 2
r/w 0 0 to 2499 ft
1 2500 to 4999 ft
2 5000 ft and above
606 Analog Input 1 Decimal Point
r/w 0 0
100
2 000
3 0000
616 Analog Input 2 Decimal Point
r/w 0 0
100
2 000
3 0000
626 Analog Input 3 Decimal Point
r/w 0 0
100
2 000
3 0000
836 Analog Range, Retransmit Output 1
r/w 0 4 to 20mA
10 to 20mA
20 to 5V
31 to 5V
41 to 10V
837 Analog Range, Retransmit Output 2
r/w 0 4 to 20mA
10 to 20mA
20 to 5V
31 to 5V
41 to 10V
305 Autotune Channel 1
r/w 0 Tune Off
1 PID Set 1
2 PID Set 2
3 PID Set 3
4 PID Set 4
5 PID Set 5
324 Autotune Channel 2
r/w 0 Tune Off
1 PID Set 6
2 PID Set 7
3 PID Set 8
4 PID Set 9
5 PID Set 10
343 Autotune Cascade
r/w 0 Tune Off
1 PID Set 1
2 PID Set 2
3 PID Set 3
4 PID Set 4
5 PID Set 5
7.2 Communications Watlow Series F4S/D
Series F4 Modbus Registers
Parameters Sorted Alphabetically
Register numbers listed are relative values. To convert to absolute values, add 40001. Registers for
profiling parameters are in a separate section at the end of this list, followed by a list of all Mod-
bus registers in numerical order. For more information about parameters, see the Index.
Page view 77
1 2 ... 73 74 75 76 77 78 79 80 81 82 83 ... 151 152