Chapter 2: Modbus-RTU Protocol
Communications Specification 23
8 data bits, least significant bit sent first
2 stop bits
No parity
Error Check Field
Cyclical Redundancy Check (CRC)
Message Framing
Messages start with a silent interval of at least 3.5 character times. This
is most easily implemented as a multiple of character times at the baud
rate that is being used on the network (shown as T1-T2-T3-T4 in the
figure below). The first field then transmitted is the device address.
The allowable characters transmitted for all fields are hexadecimal 0 to
9, A to F. Networked devices monitor the network bus continuously,
including during the silent intervals. When the first field (the address
field) is received, each device decodes it to find out if it is the addressed
device.
Following the last transmitted character, a similar interval of at least 3.5
character times marks the end of the message. A new message can begin
after this interval.
Similarly, if a new message begins earlier than 3.5 character times
following a previous message, the receiving device will consider it a
continuation of the previous message. This will set an error, as the value
in the final CRC field will not be valid for the combined messages. A
typical message frame is shown below.
Handling the Address Field
The address field of a message frame contains 8 bits. Valid slave device
addresses are in the range of 0 to 247 decimal. The individual slave
devices are assigned addresses in the range of 1 to 247 decimal. A
master addresses a slave by placing the slave address in the address field
of the message. When the slave sends its response, it places its own
address in this address field of the response to let the master know which
slave is responding.
Handling the Function Field
The function code field of a message frame contains 8 bits. Valid codes
are in the range of 1 to 255 decimal. Not all these codes are applicable to
all controllers. Current codes are described in the Function Codes
section.
START ADDRESS FUNCTION DATA CRC CHECK END
T1-T2-T3-T4 8 Bits 8 Bits
n
* 8 Bits 16 Bits T1-T2-T3-T4