Chapter 3: Controller Parameter Descriptions
Communications Specification 49
Default: 3 scans.
Output Value (8)
This parameter contains the output value, based on a full scale value of
32700 equals 100%. You can write to the output value at any time, but a
write command is only meaningful for loops set to Manual control.
Range: 0 to 32700 (0 to 100%).
Default: 0.
High Process Alarm Setpoint (9)
The high process alarm setpoint is the absolute high process variable
limit, expressed in engineering units. (This parameter is affected by the
Precision parameter.)
Range: –999 to 2500 (legal range determined by input type).
Default: 10000 (1000°F) for a J-type thermocouple.
Low Process Alarm Setpoint (10)
The low process alarm setpoint is the absolute low process variable
limit, expressed in engineering units. (This parameter is affected by the
Precision parameter.)
Range: –999 to 2500 (legal range determined by input type).
Default: 0.
Deviation Alarm Band Value (11)
The deviation alarm band value indicates the amount of deviation from
the setpoint before an alarm is issued. The amount of deviation is
expressed in engineering units. (This parameter is affected by the
Precision parameter.)
Range: 0 to 255.
Default: 5.
Alarm Deadband (12)
The alarm deadband prevents the alarm output from fluctuating rapidly
when the input is near the alarm setpoint. (This parameter is affected by
the Precision parameter.)
Range: 0 to 255.
Default: 2.