46 Communications Specification
Chapter 3: Controller Parameter Descriptions
Input Type (3)
This parameter specifies the input type.
Range: 0 to 19 defined values.
Default: 1 (J-type thermocouple).
The following input types are currently defined:
The input type determines the ranges for these other parameters:
Process variable
Setpoint
Decimal
Number
Description
Hex
Value
Range
0 Linear 00 –10 to 60 mV (scaleable)
1 J-type thermocouple 01 –350 to 1400°F
–212 to 760°C
2 K-type thermocouple 02 –450 to 2500°F
–268 to 1371°C
3 T-type thermocouple 03 –450 to 750°F
–268 to 399°C
4 S-type thermocouple 04 0 to 3200°F
–18 to 1760°C
5 R-type thermocouple 05 0 to 3210°F
–18 to 1766°C
6 B-type thermocouple 06 150 to 3200°F
660 to 1760°C
7 Pulse Input (CLS, MLS, CAS) 07 0 to 2000 Hz
8 RTD1 (high resolution)
(Not available in CLS216/16CLS and CAS200/
CAS)
08 –148 to 527°F
–100 to 275°C
9 RTD2 (low resolution)
(Not available in CLS216/16CLS and CAS200/
CAS)
09 –184 to 1544°F
–120 to 840°C
10 Skip Channel 0A N/A
11 to 13 Reserved for 8LS carbon potential N/A N/A
14 N/A N/A N/A
15 N/A N/A N/A
16 N/A N/A N/A
17 N/A N/A N/A
18 Nickel RTD
(Available in some MLS controllers)
12 –940 to 572°F
–700 to 300°C
19 Motor speed 13 –10 to 60 mV (scaleable)
20 E thermocouple 14 –328 to 1448°F
–200 to 787°C