Chapter 3: Controller Parameter Descriptions
Communications Specification 77
0 = Reverse
1 = Direct
Default: 0 for heat outputs, 1 for cool outputs.
Controller Type (99)
This parameter specifies the controller type. This is an expansion of
command 30.
Range: 0 to 3.
0 = Controller has 4 loops
1 = Controller has 8 loops
2 = Controller has 16 loops
3 = Controller has 32 loops
Ramp/Soak Profile Number (100)
This parameter specifies the assigned profile number for each loop.
Setting this to 255 indicates no profile is assigned for that loop. This is
an expansion of command 46.
Range: 0 to 255.
Default: 255 (no profile assigned).
Reference letters are assigned as follows: 0 = A, 1 = B, 2 = C, etc.
Controller Address (101)
This parameter stores the controller’s network address. Changes to this
parameter are effective the next time the controller powers up.
Range: 1 to 247.
Default: 1.
In the Anafaze/AB protocol, the controller responds to the address
stored in this parameter plus 7. For example, if this parameter is set to 1
in a controller, that controller responds to messages with a DST byte
value of 8 (1 plus 7).
Baud Rate (102)
This parameter stores the baud rate at which communications will
operate. Changes to this parameter are effective the next time the
controller powers up.
Range: 0 to 2, with these rates available:
0 = 9600
1 = 2400