Chapter 1: ANAFAZE/AB Protocol
Communications Specification 19
54 Ready Event States 1180 UC MAX_RSP *
MAX_DIGOUT_BYTES
55 Segment Setpoint 1280 SI MAX_RSP * 2 *
MAX_SEG
56 Triggers and Trigger States 1780 UC MAX_RSP*
MAX_SEG*
MAX_TRIG
57 Segment Events and Event States 1C80 UC MAX_RSP * MAX_SEG
* MAX_EVENT
58 Segment Time 2680 UI MAX_RSP * 2 *
MAX_SEG
59 Tolerance 2B80 SI MAX_RSP * 2 *
MAX_SEG
60 Ramp/Soak Flags 3080 UC MAX_CH
61 Output Limit 3200 SI MAX_CH * 4
62 Output Limit Time 3280 SI MAX_CH * 4
63 Alarm_Control 3300 UI MAX_CH * 2
64 Alarm_Acknowledge 33C0 UI MAX_CH * 2
65 Alarm_Mask 3480 UI MAX_CH * 2
66 Alarm_Enable 3540 UI MAX_CH * 2
67 Output Override Percentage 3600 SI MAX_CH * 4
68 AIM Failure Output 3690 UC 1
69 Output Linearity Curve 3700 UC MAX_CH * 2
70 SDAC Mode 3740 UC MAX_CH * 2
71 SDAC Low Value 3780 SI MAX_CH * 4
72 SDAC High Value 3800 SI MAX_CH * 4
73 Save Setup to Job 3880 UC 1
74 Input Filter 3890 UC MAX_CH
75 Loop Alarm Delay 38D0 UI MAX_CH * 2
76 Not used 3990 16
77 Loop Names
(CLS/CLS200 and MLS/MLS300)
39A0 UI MAX_CH * 2
78 T/C Failure Detection Flags
(CLS/CLS200 and MLS/MLS300)
3A30 UC MAX_CH
78 Channel Name
(CAS/CAS200)
3994 UC MAX_CH * 8
79 Restore PID Digital Input 4130 UC MAX_CH
80 Manufacturing Test 4160 UI 1
81 PV Retransmit Primary Loop
Number
4200 UC MAX_CH * 2
82 PV Retransmit Maximum Input 4250 UI MAX_CH * 4
83 PV Retransmit Maximum Output 42E0 UC MAX_CH * 2
Number Description
Address
in Hex
Type Number of Bytes
Page view 24